  Technical information

Technical Information is available for ventilation system designers, specifiers and installers to assist you in choosing the optimum GONAL system, assuring the lowest resistance with the best performance.
To ensure the correct ventilation/ extraction current building regulations demand that you take into account different factors. Those are extractor ventilation fan, the extraction and flow ratio (l/s o m3/h), ducting circuit configuration, its length, pressure loss(Pa),etc.
 
 Room
Rapid ventilation
Background ventilation
Extractor fan
 
Habitable room
 

1/20 of floor area

8.000 mm2

-
 
Kitchen
 

Window

4.000 mm2

30 l/s near worktop
 
Utility room 

Window

4.000 mm2

15 l/s
 
Bathroom
 

Window

4.000 mm2

15 l/s
 
Toilet room
 

Window

4.000 mm2

-

- Domestic building
- Without window
- Same conditions with extractor fan, with 15 minutes automatic overrun.

 Room
Rapid ventilation
Background ventilation
Extractor fan
 
Habitable room
 

1/20 of floor area
< 10 m2 4.000 mm2
< 10 m2 4.000 mm2
Non-smoking area 8 l/s/pers.
Smoking area 16 l/s/pers.
  Kitchen
Domestic Type

Window

4.000 mm2
30 l/snear worktop
60 l/s elsewhere
 
Bathroom
 

Window

4.000 mm2

15 l/s
 
Toilet room
 

1/20 of floor area

4.000 mm2
6 l/s/wc or 3 ACH


- Non Domestic building
- Without window
- Same conditions with extractor fan, with 15 minutes automatic overrun or manual   control or occupant detecting.
- All new domestic buildings and extensions must comply with F1 building regulations   and provide ventilation in kitchens, utility rooms, bathrooms and WCs.

It is essential to make the flow calculation of the area to be ventilated, to make the correct choice of GONAL ducting system.
This calculation is made by multiplying the volume by the ACH (air changes per hour) Please, see attached chart with some examples according to the current regulations.
To assure a clean air environment, always use the appropriate fan for your ventilation requirements.
By using a superior GONAL system you will be prepared for any unforeseen demand.

 Room
Air changes
per Hour
Example
Room volume
Necessary Flow
Recommended System
 
Room
 

2-4 ACH
Room
5 x 3 x 2,60 m

5x3x2,60 = 39 m3
from 78 m3/h
System 100 (600)
 
Kitchen
 

10-15 ACH
Kitchen
5 x 3 x 2,60 m

5x4x2,60= 52 m3
from 780 m3/h
System 150 (SUPRA)
 
Utility room

15-20 ACH
Utility room
4 x 3 x 2,60 m

4x3x2,60= 31,2 m3
from 468 m3/h
System 120 (800)
System 125 (DUPLA)
 
Bathroom
 

12-16 ACH
Bathroom
4 x 4 x 2,40 m

4x4x2,40= 38,4 m3
from 230 m3/h
System 120 (800)
System 125 (DUPLA)
 
Toilet room
 

3-10 ACH
Toilet room
3 x 2 x 2,40 m

3x2x2,40= 14,4 m3
from 144 m3/h
System 100 (600)
Click here to download the new catalogue